FS#4807 — UPS4
Incident Report for Network & Infrastructure
Resolved
We had an incident on the UPS (restarting). Half of the rooms 22 and 23 at Roubaix2 were impacted. The power supply of the servers was
fixed.

Update(s):

Date: 2010-11-08 12:30:22 UTC
It is still down:

Room 23 :
11 kimsufi
85 serveurs
957 rps

Room 22 :
19 kimsufi
50 serveurs
88 rps

Date: 2010-11-08 10:03:55 UTC
A human error is at the origin of the problem. The technician of the manufacturer
(EATON) was doing a standard maintenance of the UPS. Apparently, it seems that he
forgot to by-pass manually the UPS before turning it off for the maintenance.

...

The teams are in the rooms in order to re-put the servers in a working order.