OVHcloud Network Status

Current status
Legend
  • Operational
  • Degraded performance
  • Partial Outage
  • Major Outage
  • Under maintenance
FS#5004 — RBX 1 UPS 4
Incident Report for Network & Infrastructure
Resolved
After the EDF souce switch of yesterday (http://status.ovh.net/?do=details&id=982 ),
the UPS 4 at Roubaix 1 reported alamrs of a false overload downstream.

The manufacturer is intervening to solve the problem.

Update(s):

Date: 2011-01-07 18:53:49 UTC
The manufacturer replaced the measurment card (BUEI) which has a default on the version 2 that we have.

The version 4 which was installed corrects this problem.
Posted Jan 07, 2011 - 13:17 UTC